This section describes the relationship of network addresses to programmable point addresses
and instructions for setting addresses.
Each serial device must have a unique network address. For simplicity, we have established point
address ranges that are fixed to each network address. Point address ranges associated with each
network address are shown in the following table:
Network
Address
48
49
50
51
52
53
54
55
56
57
58
59
Network
Address
64
65
66
67
68*
69*
Each ZACM, except the ZACM on the CP3 board, contains a position DIP switch for network
addressing purposes. The system fixes the ZACM addresses as follows:
64 =
No Switch
65 =
# 1 On
66 =
# 1 Off
67 =
# 1 On
*Special order – see Appendix A for part numbers.
Revision 1.0
Relationship of Network Address to Point Range
ZFZA/ZTZB
ZTZB Point
Number
Addresses
1
2
11 - 20
3
21 - 30
4
31 - 40
5
41 - 50
6
51 - 60
7
61 - 70
8
71 - 80
9
81 - 90
10
91 - 100
11
101 - 110
12
111 - 120
ZACM
Associated
Number
1
2
3
4
5
A & B (10 & 11)
6
C & D (12 & 13)
"On board" ZACM
# 2 Off
# 2 On
# 2 On
Part # MAN-Z3K-01
Classic 2000 Mk II Operation Manual
Point Addresses
(ZFZA)
1 - 10
1 - 5
11 - 15
21 - 25
31 - 35
41 - 45
51 - 55
61 - 65
71 - 75
81 - 85
91 - 95
101 - 105
111 - 115
Point Addresses
SLC
(1,3,5,7) AC
1 & 2
1-126
3 & 4
1-126
5 & 6
1-126
7 & 8
1-126
1-126
1-126
(Empty)
6 - 10
16 - 20
26 - 30
36 - 40
46 - 50
56 - 60
66 - 70
76 - 80
86 - 90
96 - 100
106 - 110
116 - 120
(2,4,6,8) BD
1-126
1-126
1-126
1-126
1-126
1-126