Extinguishing Panel - INSTRUCTION MANUAL
st
nd
1
stage & 2
stage Fire Relays
The Premier EX8 has one first stage & one second stage volt free change over relay
that operates on an alarm. It is rated at 1Amp, SELV. The relay remains operated
until the panel has been reset. (note: the 1
a crossed zone OR a peripheral zone)
Fault Relay
The Premier EX8 has one volt free change over relay that operates on any fault
condition. The Relay is Normally energised, so that it gives a signal in the event of
total power failure (Mains & Battery back-up). It is rated at 1Amp, SELV. The relay
remains operated until the fault has been cleared.
Bottle Output
The Bottle Output on a Premier EX8 panel is used to drive a gas release solenoid. It
is fused @ 1 Amp.
BOTTLE +
BOTTLE -
Remote Status Outputs
The panel has the following remote outputs:-
• Abort Active
• Hold Active
• Manual release operated
• Bottle operated
• First stage alarm present
• Second stage alarm present
• Automatic mode selected
• Manual mode selected
• fault
Connecting between LED STAT + and the relevant Remote output will give a 28V
output when the signal is active. This can be used to drive a relay, or a remote
indication LED.
External Equipment Relay
The Premier EX8 has one volt free change over relay that operates AFTER the
Reset Inhibit Counter has finished. It remains active for 3 minutes, or until the reset
button is pressed. It is rated at 1Amp, SELV.
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
st
Date: 15/11/2007
stage relay operates from an alarm from
SOLENOID
VALVE
- -
+
+
10K
End of
Line Resistor
PAGE 17