1 . 2 S y s t e m O v e r v i e w

The Classic 2000 Mk II is a sophisticated microprocessor-based analog addressable fire alarm control
system suited to the various needs of commercial, industrial and institutional applications. The MkII pro-
vides the ability to "software" configure and label 1512 SLC points plus system and network points. It func-
tions in accordance with the National Fire Protection Association (NFPA) Standard 72 Fire Alarm
Code as a manual, automatic, and waterflow control system for local, central station, and remote station
applications. Activation of a compatible sensor or normally open fire alarm initiating devices will sound
audible appliances, notify a remote station, annunciate a fire or alarm condition, and energize supplemen-
tary relays.
1 . 2 . 1
L i s t o f S t a n d a r d F e a t u r e s
AC Power
110 VAC or 220 VAC 50/60Hz
Smart, Universal Power Supply
DC Power
Standard 6 Amps total (5.75 Amps available for all outputs combined)
Intelligent multi-rate battery charger
All outputs are filtered
Panel Annunciation
80-character backlit LCD
LEDs for System Alarm, System Trouble, Supervisory, AC Power, Offline, Test Mode
LED indication of silenced Alarm, Trouble, or Supervisory condition
16-button keypad for all programming and control functions
Real-time clock/calendar display
Point description, location, and condition is displayed when appropriate
Battery-backed 650+ event history log
Programming
Keypad programming on the front panel or the Remote Programming Display (RPD)
Three levels of Password protection
Auto-programming of SLC, System Devices and Network Devices
Initiating Circuits
2 Signal Line Circuits (SLC) standard, digital communication protocol, can use standard fire
rated cabling
Wire run length of up to 9,900 ft. with 14 AWG wire
126 addressable devices per SLC
SLC can be configured as Style 4, 6, or 7 without a reduction in the number of
circuits available
All SLCs are fully supervised and protected from surges
Notification Appliance/Auxiliary Power Circuits
4 programmable outputs can be either notification appliance (NAC) or auxiliary power circuits
All circuits can be configured as Style Y (Class B) or Z (Class A) without a reduction in the
number of circuits available
2.75 Amps per circuit available subject to the combined total limit of 5.75 Amps
NACs signal pattern programmable for March Time, ANSI Temporal Code, or Continuous
All circuits are fully supervised and protected from surges
Revision 1.0
Classic 2000 Mk II Operation Manual
Part # MAN-Z3K-01
Page 3