5 . 4 . 1 W a t e r f l o w P o i n t P r o g r a m m i n g
Any switch monitor module point on the SLC or any conventional input point on the serial bus may
be programmed for the waterflow function. The panel allows for the waterflow alarm to be silence-
able if required by the local authority having jurisdiction.
PLEASE NOTE: NFPA 72 requires waterflow zone alarms be non-silenceable and sound a contin-
uous output alarm. For Central Station monitored systems, no more than five waterflow devices
maybe utilized on a single switch monitor module in the Class A configuration.
To program an input point for waterflow alarm operation, follow these steps:
1. Install monitor module and connect (See Section 2, Figure W-6 for connection).
2.
module SLC address.
3. Select PROG from the menu (enter access privilege code if necessary).
4. Select 6. Points from the main programming menu.
5. Select 5. Auto-Program. Wait while the panel loads the "new" device information.
6. To access the monitor device you wish to use for the waterflow device:
Select 1. Point, then enter the loop. Press ENTER, enter the device address, then ENTER
again.
7. Select 2. Edit
8. Select 4. Options.
9. Press 1. Type until "Waterflow" is displayed, Press ENTER
10. Press 2. Label to edit the 40-character, alphanumeric label.
To associate the address with Output Group 96 which is not silenceable:
1. From the Point Edit menu, Select 3. Groups and enter Group 96.
2. Press Enter to store the new settings
3. Press RESET to update the SLC loop flags.
Review all programming selections to insure programming accuracy.
5 . 4 . 2 S u p e r v i s o r y P o i n t P r o g r a m m i n g
Any switch monitor module point on the SLC or any conventional input point on the serial bus may
be programmed for supervisory operation.
PLEASE NOTE: For NFPA applications, no more than 20 normally open supervisory devices
may be utilized on any zone.
To program an input point for supervisory alarm operation, follow these steps:
1. Install monitor module and connect (See Section 2, Figure W-6 for connection).
2. Set module SLC address.
3. Select PROG from the menu (enter access privilege code if necessary).
4. Select 6. Points from the main programming menu.
5. Select 5. Auto-Program. Wait while the panel loads the "new" device information.
6. To access the monitor device you wish to use for the waterflow device:
Select 1. Point, then enter the loop. Press ENTER, enter the device address, then
ENTER again.
7. Select 2. Edit
8. Select 4. Options.
9. Press 1. Type until "Supervisory" is displayed, Press ENTER
10. Press 2. Label to edit the 40-character, alphanumeric label.
Revision 1.0
Classic 2000 Mk II Operation Manual
Part # MAN-Z3K-01
Page 66