7. ZONE DISABLEMENT

7.1 WHY USE ZONE DISABLEMENT

To aid commissioning and assist routine maintenance checks, any of the zones or the sounder circuits can be disabled.
When a zone (or sounder cct) is disabled, the panel will not respond to any fault or fire signals it receives from that zone. This might
be used if the system requires routine maintenance, and the customer needs the system to continue running, but doesn't want
spurious false alarms.
The panel will respond in the usual manner to any events in any non-disabled zones.

7.2 TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED

Any number of zones (or the sounders) can be disabled, but it is good practice to only disable one zone at a time.
1.
Enter access code (default 1245) and press
2.
Press
for 3 seconds.
3.
Type the number of the zone you want to disable. If you wish to disable the sounders press
4.
Press
to disable the selected zone or sounders.
5.
To leave disable mode hold the
6.
The Zone and Disable LED's will be lit to show the disablement.
7.
To re-enable the zone enter the access (1245) press
8.
Press and hold
9.
Type the zone number again and press
Press and hold
for 3 seconds, Zone is now re-enabled.

7.3 IDENTIFYING DISABLED ZONES ON A PANEL SHOWING MULTIPLE EVENTS

On the infinity panel, Zones or sounder disablements are indicated by a steady GENERAL DISABLEMENT LED, along with a specific
Disablement LED.
But to allow the user to be 100% certain of the disablements if the panel is showing multiple events, momentarily pressing the
button at Access Level 2 will hide all other events for a few seconds, leaving only the Disablements visible
Approved Document No. GLT-201-7-1
Issue: 1.6
Author: NRPJ
.
button for 3 seconds.
for 3 seconds.
.