Nfpa 72 Remote Station -Networked Digital Communicator (Zndc) 7 1.4 Technical Specifications; Power Supply; Battery Charger; Notification Appliance Circuits/24Vdc Auxiliary Outputs - Zeta Classic 2000 MKII Installation And Operation Manual

January 2002,part # z6000-0001 man-z3k-01 revision 1.0
Table of Contents

Advertisement

Zeta Alarm Systems.
1 . 4
T e c h n i c a l S p e c i f i c a t i o n s
1 . 4 . 1
24VDC Power Available
5.75 -Amp Supply
7.5 -Amp Supply
Multi Rate Smart Charger
Battery Charge Current
Battery Charge Voltage
Each circuit is programmable for reverse-polarity notification circuit or 24VDC auxiliary power.
Notification Appliance Circuit Specifications
Nominal Output Voltage
Maximum Output Current
Supervision Current
End-of-line Resistor
Wiring Style Compatibility
Each circuit is supervised, power limited by an electronic circuit breaker and employs transient
voltage protection
Each Output is individually programmable by Output Group for Continuous, March Time, or
Temporal Coding output
24VDC Auxiliary Output Specifications
Nominal Output Voltage
Maximum Output Current (Each)
Non-supervised 24 VDC provided at terminal block. Power limited by an electronic circuit
breaker.
Each output is individually programmable for resettable or continuous output.
Maximum Resistance
Maximum Loop Current
Wiring Styles
All auxiliary and system relay outputs (Alarm, Trouble, and ZZRM) carry the same ratings.
Technical Specifications
Contact Type
Contact Rating
Revision 1.0
Classic 2000 Mk II Operation Manual
Nominal AC Input Voltages
120 VAC/60 Hz or 220 VAC/50 Hz
120 VAC/60 Hz or 220 VAC/50 Hz
Part # MAN-Z3K-01
Primary Current
120V/2.5A; 240V/1.5A
120V/3A, 240V/1.5A
1.5 A maximum
nominal 27.6 VDC
Outputs 1-4
24 VDC
2.75 Amps
0.5 mA
10K Ohm
Style Z, Style Y
Outputs 1-4
24.0 VDC
2.75 Amps
50 ohms
200 mA
Styles 4, 6 or 7
Form C (SPDT)
5A @ 28 VDC/30 VAC Resistive
Page 8