Zeta Alarm Systems.
To associate the address with Output Group 97 which does not ring the general alarm:
1. From the Edit menu, Select 3. Groups and enter Group 97.
2. Press Enter to store the new settings
3. Press RESET to update the SLC loop flags.
Review all programming selections to insure programming accuracy.
5 . 4 . 3 R e m o t e K e y R e s e t / S i l e n c e
To program an input point for operation as a remote keyed reset or silence station, follow these
steps:
1. Install monitor module and connect (See Section 2, Figure W-6 for connection).
2. Set module SLC address.
3. Install Remote Key Reset Station or Silence Switch as shown in device installation instruc-
tions.
4. Select PROG from the menu (enter access privilege code if necessary).
5. Select 6. Points from the main programming menu.
6. Select 5. Auto-Program. Wait while the panel loads the "new" device information.
7. To access the monitor device you wish to use for the Remote Key Reset/Silence function:
Select 1. Point, then enter the loop. Press ENTER, enter the device address, then ENTER
again.
8. Select 2. Edit
9. Select 4. Options.
10. Press 1. Type until "Rem Silence or Rem Reset" is displayed, Press ENTER
11. Press 2. Label to edit a 40-character, alphanumeric label.
Review all programming selections to insure programming accuracy.
5 . 4 . 4 F l o o r A b o v e / F l o o r B e l o w
The system can be used up to 90 stories or levels. By simply programming one output group for
each floor and inserting the floor number into the output group characteristics, the panel is pro-
grammed to activate the floor(s) above and below the floor in alarm according to the system pro-
gram Floor Configuration setting. (refer to Section 4.2.2.1 System Options)
For example, assume the panel was set up for "1 Above / 1 Below", and output group 1 was config-
ured as floor #1, output group 2 was configured as floor #2, and output group 3 was configured as
floor #3. When an input in group #2 goes into alarm, the outputs in group #2 would be activated, as
well as the outputs in group #3 (the floor above) and the outputs in group #1 (the floor below).
To achieve proper operation, the following requirements must be met:
At least one output control module or relay must be on each floor, and all notification appli-
ances on that floor must be controlled by the control module(s) or relay(s) designated for oper-
ation on that floor.
Each input point on the same floor must be associated with the output group for that floor.
Review all programming selections to insure programming accuracy.
Revision 1.0
Classic 2000 Mk II Operation Manual
Part # MAN-Z3K-01
Page 67