Zeta Alarm Systems.
There are three basic types of Modules available on the SLC loops:
Switch (Contact) Monitor Modules
I/O Module
Sounder Control (Output) Module
3 . 7 . 1 C o n t a c t M o n i t o r M o d u l e
The contact monitor module is available in two package sizes and two operating modes:
Priority Mini Monitor Module (P/N MPM-830)
Priority Monitor Module (P/N PMM-806)
The regular modules are packaged to mount into a 4-square back box. The Mini-Modules are
reduced in size to mount in a single gang box.
The priority module will interrupt the panel's polling function when initiated, and provide a faster
response to initiation. All Monitor Modules may be programmed to perform the same functions.
Contact Monitor Modules may be programmed for any of the following operations:
Alarm Input – defaults to Group 99 with associated functions – latching
Manual pull station – defaults to Group 99 with associated functions – latching
Waterflow alarm input – defaults to Group 96
Supervisory alarm input – defaults to Group 97
Remote Drill Test input – functions identical to Drill button on the LPD
Remote Reset input – functions identical to Reset button on the LPD
3 . 7 . 2 I / O M o d u l e
The input / output module functions in two modes. When selected as an I/O-input, a set of Form C
contacts follow that input (if the input is activated, the Form C contacts energize or change state).
Input defaults to Group 99. When selected as an I/O-relay, the module functions as an output and
may be included in up to 5 output groups (the input is ignored).
Note: The I/O module defaults to relay. This may be changed on the Point Edit Screen (see Appen-
dix E). Also refer to Appendix L for Mapping discussion.
3 . 7 . 3 S o u n d e r O u t p u t / S o u n d e r C o n t r o l M o d u l e
The Sounder Output modules control and supervise compatible 24VDC notification appliances.
Each Sounder Output has the following programmable attributes:
Silenceability
All Call
Output Schedule
Output Group Assignments
Courtesy Label
The Classic 2000 Mk II panel is able to communicate with up to 127 devices over an RS-485 net-
work. Network devices are both powered by and communicate through the RS-485 network. Zeta
Alarm Systems offer several devices that connect to the panel via the network, including: ZRDA,
ZTZB, ZFZA, ZRPC, ZACM, ZRLD, ZCBM, ZNDC, ZDIO, and ZPNI-S1K. See section 2 for wiring
diagrams, and section 6.0 for an in-depth explanation of the network and associated devices.
Revision 1.0
Classic 2000 Mk II Operation Manual
Part # MAN-Z3K-01
Page 49