PREMIER SX INSTALLATION MANUAL.
12. PANEL SPECIFICATIONS
12.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION
ENCLOSURE SIZE
TOP CABLE ENTRIES
BOTTOM CABLE ENTRIES
REAR CABLE ENTRIES
12.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
MAINS VOLTAGE
BATTERY VOLTAGE
SYSTEM VOLTAGE
SYSTEM VOLTAGE RIPPLE
CHARGER SIZE
ZONE VOLTAGE
SOUNDER ALARM OUTPUTS
AUXILIARY FAULT OUTPUT
AUXILIARY FIRE OUTPUT
NUMBER OF ZONES
MAXIMUM ZONE CAPACITY
MAXIMUM ZONE RESISTANCE
REMOTE SOUNDER ACTIVATION
SOUNDER ACTIVATION DELAY
ZONE END OF LINE DEVICE
SOUNDER END OF LINE DEVICE
CHARGER VOLTAGE
ZONE SHORT CIRCUIT PROTECTION
CHARGER SHORT CIRCUIT PROTECTION
TOTAL CHARGER OUTPUT
Approved Document No: GLT.MAN-101
Issue : 1.95
Authorised: GH
VALUE
355 x 275 x 100 mm
12 x 19mm DIA GROMMETED ENTRIES
2 x 19mm KNOCKOUT ENTRIES
2 SNAP OUTS, 60 x 20mm
VALUE
230V AC +/- 10% @ 50/60 Hz
24V DC (2 X 12V SLA BATTERY)
24V DC NOMINAL (18 – 32 V)
2V PK-PK MAX
UP TO 7AH in 24 Hours
21V DC NOMINAL (20 - 22.5V)
2 x 400mA @ 24V DC (Nominal)
1 x RELAY SELV (1A MAX)
1 x RELAY SELV (1A MAX)
1/2/4/6/8
32 DEVICES PER ZONE
70 ohms
VIA N/O CONTACTS
0-9 MINUTES -IN 1 MIN INCREMENTS
1N4002 DIODE (CATHODE STRIPE TO +)
10 K RESISTOR
28.4V @ 25
100mA
Batteries less than 20V
1.1 Amp
Date: 09/06/2004
o
C (NO BATTERY CONNECTED)
PAGE 16