INFINITY 8 INSTALLATION MANUAL

12. PANEL SPECIFICATIONS

12.1 ENCLOSURE SPECIFICATIONS

DESCRIPTION
ENCLOSURE SIZE
TOP CABLE ENTRIES

12.2 ELECTRICAL SPECIFICATIONS

ELECTRICAL DESCRIPTION
MAINS VOLTAGE
BATTERY VOLTAGE
SYSTEM VOLTAGE
SYSTEM VOLTAGE RIPPLE
CHARGER SIZE
ZONE VOLTAGE
SOUNDER ALARM OUTPUTS
AUXILIARY FAULT OUTPUT
AUXILIARY FIRE OUTPUT
NUMBER OF ZONES
MAXIMUM ZONE CAPACITY
SOUNDER ACTIVATION DELAY
ZONE END OF LINE DEVICE
SOUNDER END OF LINE DEVICE
CHARGER VOLTAGE
ZONE SHORT CIRCUIT PROTECTION
CHARGER SHORT CIRCUIT PROTECTION
TOTAL CHARGER OUTPUT
MAX CURRENT DRAIN FROM BATTERY (DURING MAINS FAILURE)
WHEN PSE LOAD IS I MAX A
I MAX A
I MAX B
RI MAX
Approved Document No. GLT-201-7-1
Issue: 1.6
Author: NRPJ
Date: 27/7/2012
VALUE
364 X 302 X 90 mm
15 x 20 mm DIA knock outs
VALUE
100-240V AC +/-10% @ 50/60 Hz
24V DC (2 X 12V SLA BATTERY)
24V DC NOMINAL (18 – 32 V)
2V PK-PK MAX
UP TO 3.4AH in 24 Hours
22.5V DC NOMINAL
2 x 150mA @ 24V DC (1 & 2 zone panel)
4 x 150mA @ 24V DC (4, 6, & 8 zone panel)
1 x RELAY SELV (1A MAX)
1 x RELAY SELV (1A MAX)
1/2/4/6/8
32 DEVICES PER ZONE
0-10 MINUTES - IN 1 MIN INCREMENTS
1N4002 DIODE (CATHODE STRIPE TO +)
10 K RESISTOR
o
28.6V @ 25
C (NO BATTERY CONNECTED)
40mA
Batteries less than 20V
1.15 Amp
1.0 Amp
1 Amp
1 Amp
2.8 Ω
PAGE 17