Setting Travel Limits - Genie GCL-J&H Installation Manual

Jackshaft/hoist standard duty commercial/industrial door operator
Table of Contents

Advertisement

Setting Travel Limits

UP and/or DOWN
1) If operator is in RUN mode, press CAL/RUN
2) Press SCROLL
key until display reads "UP LIMIT>CLR " or
SCROLL
"DOWN LIMIT>CLR " Figure 7.
3) Jog the door using the OPEN
desired height.
SET
4) Press SET/CLEAR
key to switch display to "UP LIMIT>SET " or
CLEAR
"DOWN LIMIT>SET ." Figure 8.
5) Press a SCROLL
key to shift to a new function and lock in the
SCROLL
limit setting.
CAL
6) Press CAL/RUN
key to return to run mode.
RUN
Resetting Travel Limits
UP and/or DOWN
1) If operator is in RUN mode, press CAL/RUN
2) Press SCROLL
key until display reads "UP LIMIT>SET " or
CROL
"DOWN LIMIT>SET." Figure 8 .
SET
3) Press SET/CLEAR
key to switch display to "UP LIMIT>CLR" or
CLEAR
"DOWN LIMIT>CLR"
4) Jog the door using the OPEN
desired height.
SET
5) Press SET/CLEAR
key to switch display to "UP LIMIT>SET" or
CLEAR
"DOWN LIMIT>SET"
CAL
6) Press CAL/RUN
key to return to run mode.
RUN
GCL-J&H
Standard Duty Operator
CAL
key to enter calibration mode.
RUN
or CLOSE
key until you reach the
OPEN
CLOSE
CAL
key to enter calibration mode.
RUN
or CLOSE
key until you reach the
OPEN
CLOSE
www.geniecompany.com
NOTE: The recommended setpoint for the DOWN Travel Limit is normally at
approximately 2 inches off the floor. This final distance will be covered by the Limit
Overrun Function to establish a more accurate seal.
CAL
RUN
DOWN LIMIT SET
CAL
RUN
OPEN
UP LIMIT CLR
CLOSE
STOP
SET
SCROLL
CLEAR
SCROLL
Figure 7
OPEN
CLOSE
STOP
SET
SCROLL
CLEAR
SCROLL
Figure 8
08-12
6.4