Sensing Edge Switch - Genie GCL-J&H Installation Manual

Jackshaft/hoist standard duty commercial/industrial door operator
Table of Contents

Advertisement

Sensing Edge Switch Installation
Figure 11 shows an example of a typical sensing edge installation. Left hand side is shown but
right hand is a mirror image of this.
1A) If wiring from sensing edge switch to operator is coiled cord or 2 wire jacketed cord:
Install junction box 12" above the center of the door opening on same side as
sensing switch.
Secure one end of cord to junction box using a cable clamp.
1B) If connection is to be made through a take up reel cord:
Install on same side as sensing edge switch and above door opening and
slightly to the side.
Install junction box adjacent to take up reel and route the stationary cord from
the reel to the box and secure with a cable clamp.
NOTE: Do not use a take-up-reel on a monitored edge. They have slip connections in them
that momentarily break contact which causes false reversals.
2)
Secure other end of cord (straight, coiled or reel) to sensing edge switch
enclosure using a cable clamp.
3)
Connect wires of cord to sensing edge switch using wire nuts or other suitable
wire connectors.
4)
Run a straight 2 wire cord from the junction box (Step 1) to the operator
electrical box.
Secure using cable clamp on each end.
5)
Join wires in cord from operator to wires in cord from switch using wire nuts or
other suitable wire connectors.
6A) Non-Monitored sensing or reversing edge connects to terminal strip on main board
s u
n i
r g
v e
r e
e s
n i
u p
s t
S .
6B) Monitored sensing or reversing edge connects to Timer-Close Module terminals
or to terminal strip on main board through OPAKMEIX.S as shown in Fig. 10B.
7)
Operate the door to make certain cord is free to travel and does not become
snared during door opening or closing.
Check sensing edge switch for proper operation.
WARNING:
Actuating the operator using constant contact on the CLOSE
button will override external reversing devices, including photocells and
reversing edges.
GCL-J&H
Standard Duty Operator
F
. g i
0 1
A
e e
.
www.geniecompany.com
Figure 10A
CONTROL SIGNAL
NOTE Non-monitored
:
N-O
sensing edge can be
REVERSE
connected directly to
these terminals. DO NOT
connect a 2-wire Monitored
sensing edge switch to
these terminals.
CONTROL SIGNAL
Figure 10B
ODC
NOTE:
2-wire monitored
STB

sensing edge switch

must be connected
through the MillerEdge
Interface Module SM-101.
INTERFACE MODULE
TIMER-CLOSE MODULE TERMINAL STRIP
MON
NOTE Monitored 2-wire
EDGE
sensing or reversing
edge can also be used
in combination with a
Timer-Close Module.
Figure 11
0 -12
TERMINAL STRIP
N-O
REVERSE
SENSING EDGE SWITCH
TERMINAL STRIP
ODC
STB
SENSING EDGE SWITCH
GND
SENSING EDGE SWITCH
5.8