Circuit Breaker and Fuse Sizes

The inverter's connections to input power must include UL Listed inverse time circuit
breakers with 600V rating, or UL Listed fuses as shown in the table below.
Input
Voltage
X200-002SFEF/NFU
X200-004SFEF/NFU
X200-005SFEF
X200-007SFEF/NFU
Single/
Three-
X200-011SFEF
Phase
X200-015SFEF/NFU
200V
X200-022SFEF/NFU
X200-037LFU
X200-055LFU
X200-075LFU
X200-004HFEF/HFU
X200-007HFEF/HFU
X200-015HFEF/HFU
Three-
X200-022HFEF/HFU
Phase
X200-030HFEF
400V
X200-040HFEF/HFU
X200-055HFEF/HFU
X200-075HFEF/HFU

Motor Overload Protection

Hitachi X200 inverters provide solid state motor overload protection, which depends on
the proper setting of the following parameters:
B012 "electronic overload protection"
B212 "electronic overload protection, 2nd motor"
Set the rated current [Amperes] of the motor(s) with the above parameters. The setting
range is 0.2 * rated current to 1.0 * rated current.
WARNING: When two or more motors are connected to the inverter, they cannot be
protected by the electronic overload protection. Install an external thermal relay on
each motor.
Inverter Model
Inverse time circuit Breaker
Distribution Fuse (Class J)
Circuit Breaker / Fuse
xv
xv
Ratings (A)
10
15
20
30
40
50
3
6
10
15
20
25