Output Logic and Timing

Logic Output Function – The inverter has a built-in logic output feature. You can select
any two of the other nine intelligent output options for internal inputs. Then, configure
the logic function to apply the logical AND, OR, or XOR (exclusive OR) operates as
desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021,
or C026 to route the logical result to terminal [11] or the relay terminals.
Intelligent outputs
used as internal
inputs:
RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC
RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC
The following table shows all four possible input combinations with each of the three
available logic operations.
Input Status
A
B
0
0
0
1
1
0
1
1
Func.
Name /
Code
SRW Display
C141
Input A select for logic
output
LogicOut1
C142
Input B select for logic
output
LogicOut2
C143
Logic function select
LogicOPE
C141
Input A
C142
Input B
[LOG] Output State
AND
OR
XOR
0
0
0
0
1
1
0
1
1
1
1
0
"C" Function
Description
11 programmable functions
available for logic (discrete)
outputs
RUN
00 RUN
03 OL
06 Dc
09 LOG
FA1
Applies a logic function to calculate
[LOG] output state,
Three options:
00 [LOG] = A AND B
01 [LOG] = A OR B
02 [LOG] = A XOR B
AND
Logic function
AND, OR, XOR
01 FA1
02 FA2
04 OD
05 AL
07 FBV
08 NDc
10 ODc
43 LOC
3 63
3 63
C021
11
C026
AL1
AL0
AL2
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
00
00
01
01
00
00

Hide quick links: