Func.
Name
Code
B133
DC bus AVR
selection
B134
Threshold voltage of
DC bus AVR setting
B140
Over-current trip
suppression
B150
Carrier mode
B151 Selection of RDY
function
Note 1:
Assume that the inverter current rating is 10000 (for B013/B213).
List of Holding Registers
R/W
Description
R/W Two option codes:
00 Disabled
01 Enabled
R/W Setting of threshold voltage of DC bus
voltage to start DC bus AVR function.
Range is:
200V class 330 to 395
400V class 660 to 790
R/W Two option codes:
00 Disable
01 Enable
R/W Automatically reduces the carrier
frequency as the ambient temperature
increases.
00 Disable
01 Enable
R/W Select Ready function.
00 Disable
01 Enable
B 35
B 35
Network Data
Reg.
Range
Res.
1176h
0, 1
1177h 330 to 395,
1 V
660 to 790
10F7h
0, 1
10F8h
0, 1
10F9h
0, 1