Hitachi X200 Series Instruction Manual page 135

X200 series inverter
Hide thumbs Also See for X200 Series:
Table of Contents

Advertisement

3 52
3 52
Option
Terminal
Code
Symbol
19
PTC
20
STA
21
STP
22
23
PID
24
PIDC
27
28
DWN
29
UDC
31
OPE
Input Function Summary Table
Function Name
PTC thermistor
Thermal Protection
Start
(3-wire interface)
Stop
(3-wire interface)
F/R
FWD, REV
(3-wire interface)
PID Disable
PID Reset
UP
Remote Control UP
Function (motorized
speed pot.)
Remote Control Down
Function (motorized
speed pot.)
Remote Control Data
Clearing
Operator Control
Description
ANLG
When a thermistor is connected to terminal [5]
and [L], the inverter checks for over-temperature
and will cause trip event and turn OFF output to
motor
OPEN
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor
ON
Starts the motor rotation
OFF
No change to present motor status
ON
Stops the motor rotation
OFF
No change to present motor status
ON
Selects the direction of motor rotation: ON =
FWD. While the motor is rotating, a change of
F/R will start a deceleration, followed by a
change in direction
OFF
Selects the direction of motor rotation: OFF =
REV. While the motor is rotating, a change of F/R
will start a deceleration, followed by a change in
direction
ON
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=01)
OFF
Has no effect on PID loop operation, which
operates normally if PID Enable is active
(A071=01)
ON
Resets the PID loop controller. The main
consequence is that the integrator sum is forced
to zero
OFF
No effect on PID controller
ON
Accelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
ON
Decelerates (decreases output frequency) motor
from current frequency
OFF
Output to motor operates normally
ON
Clears the UP/DWN frequency memory by
forcing it to equal the set frequency parameter
F001. Setting C101 must be set=00 to enable this
function to work
OFF
UP/DWN frequency memory is not changed
ON
Forces the source of the output frequency setting
A001 and the source of the Run command A002
to be from the digital operator
OFF
Source of output frequency set by A001 and
source of Run command set by A002 is used