Multi-Speed And Jog Frequency Setting - Hitachi X200 Series Instruction Manual

X200 series inverter
Hide thumbs Also See for X200 Series:
Table of Contents

Advertisement

Multi-speed and Jog Frequency Setting

The X200 inverter has the capability to store and output up to 16 preset frequencies to
the motor (A020 to A035). As in traditional motion terminology, we call this
profile
capability. These preset frequencies are selected by means of digital inputs to the
inverter. The inverter applies the current acceleration or deceleration setting to change
from the current output frequency to the new one. The first multi-speed setting is
duplicated for the second motor settings (the remaining 15 multi-speeds apply only to
the first motor).
The jog speed setting is used whenever the Jog command is active. The jog speed setting
range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The
acceleration to the jog frequency is instantaneous, but you can choose from three modes
for the best method for stopping the jog operation.
Func.
Name /
Code
SRW Display
A020
Multi-speed frequency setting
SPD 00s
A220
Multi-speed frequency
setting, 2nd motor
2SPD00s
A021
Multi-speed frequency
to
settings
A035
(for both motors)
SPD 01s
SPD 02s
SPD 03s
SPD 04s
SPD 05s
SPD 06s
SPD 07s
SPD 08s
SPD 09s
SPD 10s
SPD 11s
SPD 12s
SPD 13s
SPD 14s
SPD 15s
A038
Jog frequency setting
Jog-F
A039
Jog stop mode
Jog-Mode
"A" Function
Defines the first speed of a multi-
speed profile, range is 0.0 / start
frequency to 400Hz
0000.0Hz
A020 = Speed 0 (1st motor)
Defines the first speed of a multi-
speed profile or a 2nd motor,
range is 0.0 / start frequency to
400Hz
0000.0Hz
A220 = Speed 0 (2nd motor)
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021=Speed 1 ~ A035=Speed15
000.0Hz
A021
000.0Hz
A022
000.0Hz
A023
000.0Hz
A024
000.0Hz
A025
000.0Hz
A026
000.0Hz
A027
000.0Hz
A028
000.0Hz
A029
000.0Hz
A030
000.0Hz
A031
000.0Hz
A032
000.0Hz
A033
000.0Hz
A034
000.0Hz
A035
Defines limited speed for jog,
range is 0.00 / start frequency to
001.00Hz
9.99 Hz
Define how end of jog stops the
motor; three options:
00 Free-run stop
01 Controlled deceleration
02 DC braking to stop
FRS
Description
3 15
3 15
multi-speed
Run
Defaults
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
0.0
0.0
Hz
0.0
0.0
Hz
See
See
Hz
next
next
row
row
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.00
1.00
Hz
00
00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents