Inverter Parameter Setup - Hitachi X200 Series Instruction Manual

X200 series inverter
Hide thumbs Also See for X200 Series:
Table of Contents

Advertisement

6. Inverter Parameter Setup - The inverter has several settings related to ModBus
communications. The table below lists them together. The
which parameters
refer to the host computer documentation in order to match some of its settings.
Func.
Name
Code
A001
Frequency source setting
A002
Run command source setting
B089
Monitor display select for
networked inverter
C070
Selection of OPE/ModBus
C071
Communication speed selection
C072
Node allocation
C074
Communication parity selection
C075
Communication stop bit selection
C076
Communication error select
C077
Communication error time-out
C078
Communication wait time
NOTE: When you edit and store any of the parameters above, the inverter causes it to
take effect immediately. ModBus transmission occurs only after you set the OPE/485
DIP switch to the "485" position and turn on the inverter again. Note that parameters
C070 to C078 cannot be changed via the network. To edit them, you must disconnect the
inverter from the ModBus and wait for about 30sec until the inverter's internal keypad
begin functioning. Then use this keypad to edit the parameters. Please don't connect
other external programming devices to RJ45 connector, because the bus mode is in
RS485 mode. It may cause the inverter or external programming devices to be damaged
when DIP switch is in "485" position.
must
be set properly to allow communications. You may need to
Required
Required
Settings
00 Keypad potentiometer
01 Control terminal
02 Function F001 setting
03 ModBus network input
10
Calculate function output
01 Control terminal
02 Run key on keypad, or digital operator
03
ModBus network input
01 Output frequency monitor
02 Output current monitor
03 Rotation direction monitor
04 Process variable (PV), PID feedback
monitor
05 Intelligent input terminal status
06 Intelligent output terminal status
07 Scaled output frequency monitor
02...OPE or option
03...ModBus (485)
04 4800 bps
05 9600 bps
06 19200 bps
Network address, range is 1 to 32
00 No parity
01 Even parity
02 Odd parity
Range is 1 to 2
00 Trip (Error code E60)
01 Decelerate to a stop and trip (Error code
E60)
02 Disable
03 Free run stop (coasting)
04 Decelerate to a stop
Comm. Watchdog timer period,
range is 0.00 to 99.99 sec.
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. ms
B 5
B 5
column indicates