The following table lists the holding registers for the "A" Group Standard Functions.
Func.
Name
Code
A001
Frequency source
setting
A002
Run command source
setting
A003
Base frequency setting R/W Settable from 30 Hz to the
A203
Base frequency setting,
2nd motor
A004
Maximum frequency
setting
A204
Maximum frequency
setting, 2nd motor
A005
[AT] selection
A011
O–L input active range
start frequency
A012
O–L input active range
end frequency
A013
O–L input active range
start voltage
A014
O–L input active range
end voltage
A015
O–L input start
frequency enable
A016
External frequency
filter time constant
List of Holding Registers
R/W
Description
R/W Five options; select codes:
00...Keypad potentiometer
01...Control terminal
02...Function F001 setting
03...ModBus network input
10...Calculate function output
R/W Three options; select codes:
01...Control terminal
02...Run key on keypad, or
digital operator
03...ModBus network input
maximum frequency
R/W Settable from 30 Hz to the 2nd
maximum frequency
R/W Settable from the base frequency
up to 400 Hz
R/W Settable from the 2nd base
frequency up to 400 Hz
R/W Five options, select codes:
00... Select between [O] and [OI]
at [AT]
02... Select between [O] and
keypad potentiometer
03... Select between [OI] and
keypad potentiometer
04... Only [O] input active
05... Only [OI] input active
R/W The output frequency
corresponding to the analog
input range starting point,
Range is 0.0 to 400.0
R/W The output frequency
corresponding to the analog
input range ending point, range
is 0.0 to 400.0
R/W The starting point (offset) for the
active analog input range, range
is 0. to 100
R/W The ending point (offset) for the
active analog input range, range
is 0. to 100.
R/W Two options; select codes:
00...Use offset (A011 value)
01...Use 0 Hz
R/W Range n = 1 to 16, where n =
number of samples for average.
Set 17 to use 16-samples for avg.,
plus deadband +0.1/-0.2Hz
B 25
B 25
Network Data
Reg.
Range
Res.
1019h
0 to 3, 10
101Ah
1, 2, 3
101Bh 30 to max.
1 Hz
freq.
150Ch 30 to max.
1 Hz
freq.2
101Ch
30 to 400
1 Hz
150Dh
30 to 400
1 Hz
101Dh
0, 2, 3,
4, 5
1020h
0 to 4000
0.1 Hz
1022h
0 to 4000
0.1 Hz
1023h
0 to 100
1 %
1024h
0 to 100
1 %
1025h
0, 1
1026h
1 to 17
1 sample