Additional Analog Input Settings

Input Range Settings – The parameters in the following table adjust the input
characteristics of the analog current input. When using the inputs to command the
inverter output frequency, these parameters adjust the starting and ending ranges for
the current, as well as the output frequency range. Related characteristic diagrams are
located in "
Analog sampling setting is the value specified in A016.
Func.
Code
A101
[OI]-[L] input active range
start frequency
OI-EXS
A102
[OI]-[L] input active range
end frequency
OI-EXE
A103
[OI]-[L] input active range
start current
OI-EX%S
A104
[OI]-[L] input active range
end voltage
OI-EX%E
A105
[OI]-[L] input start frequency
enable
OI-LVL
Refer to parameter A011 to A015 for analog voltage input.
NOTE: You cannot use voltage input and current input ([O] and [OI] input) at the same
time on the X200 series inverter. Please do not connect the cable to [O] and [OI]
terminals at the same time.
Analog Input Settings " on page 3-13.
"A" Function
Name /
SRW Display
The output frequency
corresponding to the analog input
range starting point,
range is 0.0 to 400.0 Hz
0000.0Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
0000.0Hz
The starting point (offset) for the
current input range,
00000%
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
00000%
Two options; select codes:
00 Use offset (A101 value)
0Hz
01 Use 0Hz
Description
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
0.0
0.0
Hz
0.0
0.0
Hz
0.
0.
%
100.
100.
%
01
01