Output Function Summary Table - Hitachi X200 Series Instruction Manual

X200 series inverter
Hide thumbs Also See for X200 Series:
Table of Contents

Advertisement

Output Function Summary Table – This table shows all twelve functions for the logical
outputs (terminals [11] and [AL]) at a glance. Detailed descriptions of these functions,
related parameters and settings, and example wiring diagrams are in
Output Terminals" on page
Option
Terminal
Code
Symbol
00
RUN
Run Signal
01
FA1
Frequency Arrival Type
1–Constant Speed
02
FA2
Frequency Arrival Type
2–Over frequency
03
OL
Overload Advance
Notice Signal
04
OD
Output Deviation for
PID Control
05
AL
Alarm Signal
06
Dc
Analog Input
Disconnect Detect
07
FBV
PID Second Stage
Output
08
NDc
Network Detection
Signal
09
LOG
Logic Output Function
10
ODc
Communication option
error
43
LOC
Low load detection
4-34.

Output Function Summary Table

Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Description
When the inverter is in Run Mode
When the inverter is in Stop Mode
When output to motor is at the set frequency
When output to motor is OFF, or in any
acceleration or deceleration ramp
When output to motor is at or above the set
frequency, even if in accel. or decel rams
When output to motor is OFF, or at a level
below the set frequency
When output current is more than the set
threshold for the overload signal
When output current is less than the set
threshold for the deviation signal
When PID error is more than the set threshold
for the deviation signal
When PID error is less than the set threshold
for the deviation signal
When an alarm signal has occurred and has not
been cleared
When no alarm has occurred since the last
cleaning of alarm(s)
When the [O] input value < B082 setting (signal
loss detected), or the [OI] input current < 4mA
When no signal loss is detected
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053)
Transitions to OFF when the PID Process
Variable (PV) exceeds the PID High Limit
(C052), and transitions to OFF when the
inverter goes from Run Mode to Stop Mode
When the communications watchdog timer
(period specified by C077) has time out
When the communications watchdog timer is
satisfied by regular communications activity
When the Boolean operation specified by C143
has a logical "1" result
When the Boolean operation specified by C143
has a logical "0" result
No communication between communication
option is detected during a time set in P044
Communication is normal
Motor current is less than the set value of C039
Motor current is not less than the set value of
C039
3 55