Honeywell DCP301 User Manual page 94

Digital program controller
Table of Contents

Advertisement

No.
Item Code
M .-C
29
Motor control
method selection
M .-A T
30
Motor valve opening
automatic adjust-
ment
M .-C L
31
Motor valve opening
adjustment fully
closed position
M .-O P
Motor valve opening
32
adjustment fully
open position
M .-T
Motor valve opening
33
adjustment fully
open/closed time
Item
Factory
User
Setting
Setting
0
0
1000
9000
30.0
Chapter 7. PARAMETER SETUP
Setting
0: MFB control (conventional) + estimated position
control
1: MFB control (conventional) only
2: Estimated position control only
[Note]
On models other than 2G output models, "– – – –" is
displayed and setting is not possible.
0: Adjustment disabled
1: Adjustment enabled
[Note]
On models other than 2G output models, "– – – –" is
displayed and setting is not possible.
On 2G output models, when
" is displayed and setting is not possible.
0 to (fully open adjustment - 500)
[Note]
On models other than 2G output models, "– – – –" is
displayed and setting is not possible.
On 2G output models, when
" is displayed and setting is not possible.
(fully closed adjustment + 500) to 9999
[Note]
On models other than 2G output models, "– – – –" is
displayed and setting is not possible.
On 2G output models, when
" is displayed and setting is not possible.
5.0 to 240.0s
[Note]
On models other than 2G output models, "– – – –" is
displayed and setting is not possible.
M .-C
setting is 2, "– – – –
M .-C
setting is 2, "– – – –
M .-C
setting is 2, "– – – –
7-9