Pv Calibration - Honeywell DCP301 User Manual

Digital program controller
Table of Contents

Advertisement

Chapter 11. CALIBRATION

PV calibration

Gain No. select
PV zero, span
11-10
keys to show (
Scroll , ,
, or
key.
Press PARA key until the PROG/SEG display shows (01-01). Connect calibration
device (See Section "11-3 Set Up").
Input the gain number (See Table 11-9 and Table 11-10) by scrolling , ,
keys the upper display ( ENT key not required).
(1) PV zero adjustment
(a) Press PARA key until the PROG/SEG display shows (
(b) Adjust your calibration device to an output signal equal to the 0% range value
(See Table 11-9), the signal need to be on the input for 10 to 15 seconds.
(c) Press ENT key after display stabilizes.
(2) PV span adjustment
(a) Press PARA key until the PROG/SEG display shows (
(b) Adjust your calibration device to an output signal equal to the 100% range value
(See Table 11-9 and table 11-10).
(c) Press ENT key after display stabilizes.
Table 11-9.
Gain No.
PV Input 0% PV Input 100%
0
–12.785mV
1
–8.565mV
2
–13.788mV
3
–12.000mV
4
–1.000mV
5
–0.100V
6
–0.500V
7
–1.000V
8
0.000mA
9
10.000
10
10.000
11
0.000
12
0.000
Table 11-10.
Gain No.
PV Input 0% PV Input 100%
16
–8.000mV
17
–20.000mV
18
–1.000V
19
10.000
20
0.000
1.0.1.1.
) on upper display, then press ENT
Connecting Position
110.000mV
Between 34(+) and 33(–)
58.303mV
Between 34(+) and 33(–)
40.481mV
Between 34(+) and 33(–)
23.300mV
Between 34(+) and 33(–)
11.000mV
Between 34(+) and 33(–)
1.100V
Between 34(+) and 33(–)
5.500V
Between 34(+) and 33(–)
11.000V
Between 34(+) and 33(–)
22.000mA
Between 34(+) and 33(–)
480.000
Between 34 and 33
178.000
Between 34 and 33
110.000
Between 34 and 33
45.000
Between 34 and 33
Connecting Position
20.000mV
Between 28(+) and 29(–)
70.500mV
Between 28(+) and 29(–)
11.000V
Between 27(+) and 26(–)
380.000
Between 30 and 29
110.000
Between 30 and 29
, or
01-02
).
01-03
).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents