Chapter 4. WIRING

Voltage output (6D)

Handling Precautions

Heat/cool output (3D)

Handling Precautions

Heat/cool output (5K)

Handling Precautions
4-10
Connect as follows.
11
SSR
12
13
Voltage output is reliant on an internal fixed-current circuit.
Set the current value in the setup data so that the optimum voltage is obtained
matched to the conditions of the SSR in use and load.
Factory setting: general-purpose SSR voltage value.
Connect as follows.
11
Load
12
Power supply
13
14
Load
15
Power supply
16
When switching small currents, connect a bleeder resistor to allow current flow of
the minimum relay switching input (100mA min.).
Connect as follows.
11
Load
(SSR)
12
13
14
Load
(SSR)
15
16
Current output and voltage output can be selected by setups C 7 5 and C 7 6.
Voltage output is reliant on an internal fixed-current circuit.
Set the current value in the setup data so that the optimum voltage is obtained
matched to the conditions of the SSR in use and load.
Factory setting: general-purpose SSR voltage value.
2 to 22mAdc
With current adjustment function
(setup: C 7 8 )
Output 1
Contact rating, resistive load
5A (30Vdc/120Vac)
4A (240Vac)
Minimum switching current: 100mA
Output 2
Contact rating, resistive load
5A (30Vdc/120Vac)
4A (240Vac)
Minimum switching current: 100mA
Output 1
Current output:
4 to 20/0 to 20mAdc
Load resistance 600 max.
• Voltage output:
2 to 22mAdc
With current adjustment function (setup: C 7 8 )
Output 2
Current output:
4 to 20/0 to 20mAdc
Load resistance 600 max.
Voltage output:
2 to 22mAdc
With current adjustment function (setup: C 7 9 )