Chapter 11. CALIBRATION
00-02
Display test (
00-03
Digital input test (
Upper
Display
0.0.0.0.
0.0.0.1.
0.0.0.2.
0.0.0.4.
0.0.0.8.
0.0.1.0.
0.0.2.0.
0.0.4.0.
0.0.8.0.
0.1.0.0.
0.2.0.0.
0.4.0.0.
0.8.0.0.
Notes: 1. "ON" means to short the terminals by a jumper.
11-8
)
Press PARA key until the display test starts.
Then, each 7-segment LED, LED indicators and LCD illuminates at every 0.5 sec.
This is to check if each LED/LCD illuminates.
)
Press PARA key until the PROG/SEG display shows (
When you turn on or off each remote switch, the upper display will show the data
described in Table 11-4.
Table 11-4. DI
DI
(21)
(22)
Terminal
Number
(25)
(25)
ON
ON
2. "—" means to open the terminals.
Example:
(21)
= Short (21) and (25) terminals.
(25)
ON
(23)
(24)
(41)
(42)
(43)
(25)
(25)
(25)
(25)
(25)
ON
ON
ON
ON
ON
00-03
).
(44)
(45)
(46)
(47)
(48)
(25)
(25)
(25)
(25)
(25)
ON
ON
ON
ON
ON