Parameter Setup List; Variable Parameter Settings "P A R A - Honeywell DCP301 User Manual

Digital program controller
Table of Contents

Advertisement

7-3

Parameter Setup List

Note

Variable parameter settings "P A R A"

No.
Item Code
L O C
1
Key lock
P R T C
Program protect
2
F L
Input 1 digital filter
3
P B 1
Input 1 bias
4
S B 1
SP1 bias
5
O T L
MV change limitter
6
(CH1)
1 O U T
PID operation initial
7
MV (CH1)
R P 1 D
PID operation
8
initialization
A T
Auto-tuning method
9
selection (CH1)
S T
Smart-tuning
10
method selection
(CH1)
2 P 1 D
11
Advanced PID
selection (CH1)
"U" and "%FS" used in the "Factory Setting" and "Setting" columns in the table mean
the following:
U:
The decimal point changes according to the input range type setting. For example,
when one digit past the decimal point is allowed, -1999U becomes 199.9, and
9999U becomes 999.9.
%FS: The numbers and decimal point position changes according to the input range setting.
For example, when the input range is 0.0 to 800.0 C, 0%FS is 0.0 and 100%FS is
800.0.
Item
Factory
Setting
0
0
0.0
0U
0U
0.0
0.0
(50.0)
0
0
0
0
User
Setting
0: Key lock disabled
1: Display of setup data settings disabled
2: Display of parameter settings and program settings
disabled
3: Use of operation keys disabled
4: Display of parameter settings and program settings
displayed, and use of operation keys disabled
[Note]
Two or more key lock setting values for actual key lock
items and items assigned to
and set.
0: Changing program settings enabled
1: Changing program settings disabled
0.0 to 120.0s
[Note]
0.0 disables the filter.
-1000 to 1000U
-1999 to 9999U
0.0 to 10.0% (0.1%s steps)
[Note]
0.0 disables the limit.
0.0 to 100%
[Note]
On heat/cool models, the factory setting is 50.0.
0: Automatic judgment of initialization is carried out by
advance operation.
1: Initialization is carried out by advance operation.
2: Initialization is not carried out by advance operation.
0: AT is disabled.
1: General AT is executed.
2: Overshoot-inhibited AT is executed.
3: AT by neural net is executed.
[Note]
On heat/cool models, "– – – –" is displayed, and
setting is not possible.
0: Smart-tuning is disabled.
1: The brake value is fixed to inhibit overshoot.
2: Overshoot is inhibited while automatically reviewing
the brake value.
[Note]
On heat/cool models, "– – – –" is displayed, and
setting is not possible.
0: 2 degrees of freedom PID is disabled.
1: 2 degrees of freedom PID is enabled.
[Note]
On heat/cool models, "– – – –" is displayed, and
setting is not possible.
Chapter 7. PARAMETER SETUP
Setting
PARA
can be displayed
7-7