A Specifications

Power Requirements

Table A-1. Power Requirements
Voltage and frequency
Maximum continuous power
input
Maximum inrush current
Delayed action circuit breaker
recommended
Power availability
NOTE
The HP NetServer LXr Pro8 includes a total of four power
supplies. The system requires three functional supplies at all
times; individual supplies can be hot-swapped.

Space Requirements

Table A-2. Space Requirements
System dimensions
Rack space
Rack clearance
System weight
200-240 VAC; 47-63Hz.
1560W
80A for 10 ms
208/240 60hz: NEMA AB1 20A
220/230/240 50hz -- IEC MCB 16A, type C (single
server per rack) or type D (multiple servers per rack).
200W continuous to PCI cards and internal drives
17.5 in. high x 19.0 in wide x 32.1 in deep
(44.5 cm high x 48.6 cm wide x 81.53 cm deep)
10 EIA units
46 in. (117 cm) beyond rear of HP rack (door mounted)
30 in. (76 cm) beyond rear of HP rack (no door)
170 lb. (76 kg)
105