Setting Mode
Upper Limit (H) of Linear Output Range
lset.h
Lower Limit (L) of Linear Output Range
lset.l
FUNCTION
SETTING
REFERENCE
MODELS
64
Linear output setting is made in the option menu to enable the K3NP to have
voltage or current output in proportion to the change in display value.
· The maximum and minimum values of linear output are set in this parameter.
Linear output
20 mA or 5 V
4 mA or 1 V
· L can be greater or less than H.
· L cannot be the same as H, otherwise H will be automatically set to a value
obtained by adding 1 to L.
· The teaching function can be used for setting linear output ranges.
Setting range
0 to 99999
H linear output range
L linear output range
Refer to 6-1 Teaching Function.
This setting is available for the K3NP with the Linear Output Board.
Section 4-2
Display value
Default
99999
0