Omron K3NP - 1998 Operation Manual page 71

Period meter
Table of Contents

Advertisement

Setting Mode
62
Level Output
LL, L, H, or HH Comparative Output:
Turns ON when the measured value exceeds the LL, L, H, or HH setting value.
PASS Output:
Turns ON when the LL, L, H, and HH comparative outputs are all OFF.
HH setting value
H setting value
L setting value
LL setting value
HH comparative output
H comparative output
PASS
L comparative output
LL comparative output
Zone Output
HH Comparative Output:
Turns ON when the measured value exceeds the HH setting value.
H Comparative Output:
Turns ON when the measured value is between the H and HH setting values.
PASS Output:
Turns ON when the measured value is between the L and H setting values.
L Comparative Output:
Turns ON when the measured value is between the LL and L setting values.
LL Comparative Output:
Turns ON when the measured value falls below the LL setting value.
Be sure to set the setting values so they satisfy the following formula:
LL < L < H < HH
HH setting value
H setting value
L setting value
LL setting value
HH comparative output
H comparative output
PASS
L comparative output
LL comparative output
Section 4-2
Measured value
Measured value