Prescaling Menu ( Pscl ); Bank No. Of Prescale; Prescaling Value X (Mantissa) Of Input A ( Ps*.Ax ); Prescaling Value Y (Exponent) Of Input A ( Ps*.Ay ) - Omron K3NP - 1998 Operation Manual

Period meter
Table of Contents

Advertisement

Setting Mode

4-2-4 Prescaling Menu ( pscl )

Bank No. of Prescale

p.bank
Prescaling Value X (Mantissa) of Input A
ps*.ax
Prescaling Value Y (Exponent) of Input A
ps*.ay
Decimal Point Position
decp.*
FUNCTION
SETTING
REFERENCE
SETTING
Follow the steps described below to input the following.
EXAMPLE
1, 2, 3...
46
The measured data of passing speed or cycle is displayed after being multiplied
by a preset value (i.e., prescaling value).
Display value = Measured data x Prescaling value
Input type
p.bank: Bank no. of prescale
ps*.ax: Prescaling value X (mantissa)
of input A
ps*.ay: Prescaling value Y (exponent)
of input A
decp.*: Decimal point position
Refer to Section 3 Operating Modes.
Operating mode = F1
Prescaling bank = OFF
Prescaling value X (mantissa) of input A = 0.5000
Prescaling value Y (exponent) of input A = --1
Decimal point = jjjj.j (First digit from the right)
Set Value LED Display Model
1. Press the Mode Key for more than one second while the pscl prescaling
menu is displayed. The p.bank prescaling bank setting will be displayed.
Set Value LED Display Model
Section 4-2
Setting
off/1 to 4
0.0001 to 9.9999
--9 to 9
One of the 1st to 4th digits
from the right
Basic Model
Basic Model
Default
off
1.0000
0
No decimal
point
position
setting