DM Area Setup Example
Point A
positioning
Initial
frequency
Point B
positioning
Address
Value
D0000
07D0
Acceleration ratio: 2000 (Hz/4ms)
D0001
07D0
Deceleration ratio: 2000 (Hz/4ms)
D0002
C350
Target frequency: 50000 (Hz)
D0003
0000
D0004
FC18
Pulse output volume: -1000 (Hz)
D0005
FFFF
D0006
0000
Initial frequency: 0 (Hz)
D0007
0000
D0010
07D0
Acceleration ratio: 2000 (Hz/4ms)
D0011
07D0
Deceleration ratio: 2000 (Hz/4ms)
D0012
C350
Target frequency: 50000 (Hz)
D0013
0000
D0014
86A0
Pulse output volume: 100000 (Hz)
D0015
0001