Cycle Time/High-speed Processing
6-1-2
Maximum Cycle Time (Watch Cycle Time)
264
The following table shows the corresponding settings when using a Program-
ming Console.
Programming
Console
address
+208, bits 0 to
Minimum Cycle Time
3
If the cycle time (see note) exceeds the maximum cycle time setting, the
Cycle Time Too Long Flag (A40108) will be turned ON and PLC operation will
be stopped.
Note Indicates the cycle time for program execution when using parallel
processing mode.
PLC Setup
When using the CX-Programmer, make the settings on the Timings Tab Page.
The following table shows the corresponding settings when using a Program-
ming Console.
Programming
Console
address
+209, bit 15
Enable Watch Cycle
Time Setting
+209, bits 0 to
Watch Cycle Time
14
Setting
(Enabled when bit 15
is set to 1.)
Auxiliary Area Flags and Words
Name
Cycle Time Too Long
Flag
Note If the peripheral servicing cycle exceeds 2.0 s, a peripheral servicing cycle
time exceeded error will occur and the CPU Unit will stop operation. If this
happens, A40515 (Peripheral Servicing Cycle Time Over Flag) will turn ON.
Name
0001 to 7D00: 1 to 32,000 ms
(1-ms units)
Name
0: Default (1s)
1: Bits 0 to 14
001 to FA0: 10 to 40,000 ms
(10-ms units)
Address
A40108
A40108 will be turned ON and the CPU Unit
will stop operation if the cycle time exceeds the
watch cycle time setting. The "cycle time"
would be the program execution time when
using a Parallel Processing Mode for CS1-H,
CJ1-H, or CJ1M CPU Units, or CS1D CPU
Units for Single-CPU Systems.
Section 6-1
Setting
Default
0000 (no
minimum)
Setting
Default
0001 (1 s)
Description