Cycle Time/High-speed Processing

6-1

Cycle Time/High-speed Processing

6-1-1

Minimum Cycle Time

6-1-2

Maximum Cycle Time (Watch Cycle Time)

208
The following functions are described in this section
• Minimum cycle time function
• Maximum cycle time function (watch cycle time)
• Cycle time monitoring
• Quick-response inputs
• Interrupt functions
• I/O refreshing methods
• Disabling Special I/O Unit cyclic refreshing
A minimum (or fixed) cycle time can be set in CS/CJ-series PCs. Variations in
I/O response times can be eliminated by repeating the program with a fixed
cycle time.
The minimum cycle time (1 to 32,000 ms) is specified in the PC Setup in1-ms
units.
Minimum cycle time
(Effective)
Actual cycle time
If the actual cycle time is longer than the minimum cycle time, the minimum
cycle time function will be ineffective and the cycle time will vary from cycle to
cycle.
Minimum cycle time
Actual cycle time
(Effective)
PC Setup
Address
Name
208
Minimum Cycle Time
Bits: 0 to 15
If the cycle time exceeds the maximum cycle time setting, the Cycle Time Too
Long Flag (A40108) will be turned ON and PC operation will be stopped.
PC Setup
Address
Name
209
Enable Watch Cycle
Bit: 15
Time Setting
209
Watch Cycle Time
Bits: 0 to 14
Setting
(Enabled when bit 15
is set to 1.)
Minimum cycle time
Minimum cycle time
(Effective)
(Effective)
Actual cycle time
Actual cycle time
Minimum cycle time
Minimum cycle time
Actual cycle time
Actual cycle time
(Effective)
Setting
0001 to 7D00: 1 to 32,000 ms
(1-ms units)
Setting
0: Default (1s)
1: Bits 0 to 14
001 to FA0: 10 to 40,000 ms
(10-ms units)
Section 6-1
(Effective)
Default
0000 (no
minimum)
Default
0
001 (10 ms)