Omron CJ - PROGRAMMING MANUAL 12-2009 Programming Manual page 345

Programmable controllers
Table of Contents

Advertisement

Serial Communications
Sending FINS Messages
Using CMND(490) in CPU
Unit's Ladder Program
CPU Unit with unit version 3.0 or later
RS-232C port
Protocol
conversion
FINS message-to-serial
CPU Unit with unit
version 3.0 or later
Protocol
conversion
CPU Unit's serial port
Peripheral port
RS-232C port
2. The contents of the CompoWay/F command enclosed in the FINS mes-
sage that is sent is as follows:
Node number + subaddress + SID + command text (ASCII must be used.)
STX, ETX+BCC are not required when sending FINS. They are added au-
tomatically for serial communications.
The CPU Unit converts the FINS messages to CompoWay/F protocol for
sending in this operation.
Access from CPU Unit (on the Same PLC)
Serial conversion
CMND(490)
FINS message
CompoWay/F
2803
FINS header
command
CompoWay/F
command
RS-485 (CompoWay/F)
CompoWay/F-compatible
OMRON component
Access from CPU Unit (PLC on the Network)
CMND(490)
FINS message
CompoWay/F
FINS header
2803
command
Network (Ethernet, Controller
Link, DeviceNet)
CompoWay/F
command
RS-485 (CompoWay/F)
CompoWay/F-compatible
OMRON component
Serial port's unit address
FD hex (253 decimal)
FC hex (252 decimal)
Details
OMRON components
connected serially to
the CPU Unit's RS-
232C port using Com-
poWay/F can be
accessed from a CPU
Unit in the same PLC.
Details
OMRON components
connected serially to
the CPU Unit's RS-
232C port using Com-
poWay/F can be
accessed from a CPU
Unit in a PLC con-
nected to the network.
Section 6-3
Routing tables to
treat serial
communications path
as network
Optional
Routing tables to
treat serial
communications path
as network
Optional
305

Hide quick links: