Serial Communications
Item
RS-232C
Serial communica-
port setting
tions mode
Port baud rate
Link method
Number of link
words
Highest unit num-
ber
Settings at the Polled Unit
When using a standard serial PLC Link, select the Standard Option in the
Communications Settings Area.
The following table shows the corresponding settings when using a Program-
ming Console.
Programming Console
address
Word
Bit
+160
11 to 08
+161
07 to 00
+166
15
07 to 04
03 to 00
Note Automatically allocates 10 words (A hex) when the default setting of 0 hex is
used.
When using a high-speed serial PLC Link, select the Custom Option in the
Communications Settings Area and set the baud rate to 115,200 bps.
Set value
8 hex: Serial PLC Links
Polling Unit
00 to 09 hex: Standard
0A hex: High-speed
0: Complete links
1: Polling Unit links
1 to A hex
0 to 7 hex
Section 6-3
Default
Refresh timing
0 hex
Every cycle
00 hex
0
0 hex
(See note.)
0 hex
311