6.9 Diagnosing and Resetting Faults

6.9
Diagnosing and Resetting Faults
When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault,
then restart the drive.

◆ Fault Occurs Simultaneously with Power Loss

WARNING! Electrical Shock Hazard. Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or
between the ground and main circuit terminals before restarting the drive. Failure to comply may result in serious injury or death and
will cause damage to equipment.
1.
Turn on the drive input power.
2.
Use monitor parameters U2-
occurred.
3.
Remove the cause of the fault and reset.
Note: 1. To find out what faults were triggered, check the fault history in U2-02. Information on drive status when the fault occurred such as
the frequency, current, and voltage can be found in U2-03 through U2-20.
page 334
for information on how to view fault data.
2. When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.

◆ If the Drive Still has Power After a Fault Occurs

1.
Look at the digital operator for information on the fault that occurred.
2.
Refer to Fault Displays, Causes, and Possible Solutions on page 306
3.
Reset the fault.

◆ Viewing Fault Trace Data After Fault

1.
Turn on the drive input power. The first screen displays.
2.
Press
or
until the monitor screen is displayed.
3.
Press
to display the parameter setting screen.
Press
and
to scroll to monitor U2-02. The fault code
4.
shown in U2-02 is the fault that occurred last.
Press
to view drive status information when fault occurred.
7.
Parameters U2-03 through U2-20 help determine the cause of a fault.
Parameters to be monitored differ depending on the control mode.
334
to display data on the operating status of the drive just before the fault
Refer to Fault Reset Methods on page
Step
Refer to Viewing Fault Trace Data After Fault on
335.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Display/Result
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD
FWD/REV
- MODE -
DRV
Rdy
Monitor Menu
U1-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD
FWD/REV
-MONITR-
DRV
Rdy
Monitor
U1
-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD
FWD/REV
- MONITR -
DRV
Rdy
Last Fault
U2-02= oC
U2-03= 0.00Hz
LSEQ
U2-04= 0.00Hz
LREF
JOG
FWD
FWD/REV
- MONITR -
DRV
Rdy
Frequency Ref
U2-03= 0.00Hz
U2-04= 0.00Hz
LSEQ
U2-05= 0.00A
LREF
JOG
FWD
FWD/REV
- MONITR -
DRV
Rdy
Heatsink Temp
U2-20= XX °C
U2-01= -----
LSEQ
U2-02= -----
LREF
JOG
FWD
FWD/REV