◆ A2: User Parameters

A2-01 to A2-32: User Parameters 1 to 32
The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the
parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to
this list.
No.
A2-01 to A2-32
<1> A1-06 determines how parameters edited by the user are saved to the list of Preferred Parameters, A2-01 through A2-32. Refer to
Selection on page 103
for details.
Saving User Parameters
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2).
Next assign the parameter number to the User Parameters list by entering it into one of the A2-
is then set to 1, the access level can be restricted so that users can only set and refer to the specific parameters saved as
User Parameters.
A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
No.
A2-33
Setting 0: Do not save list of recently viewed parameters.
To manually select the parameters listed in the User Parameter group, set A2-33 to 0.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A
total of 16 parameters are saved with the most recently edited parameter set to A2-17, the second most recently to A2-18,
and so on. User Parameters can be accessed using the Setup Mode of the digital operator.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
User Parameters 1 to 32
Parameter Name
User Parameter Automatic Selection
5.1 A: Initialization
Setting Range
Default
b1-01 to o2-08
Determined by A1-06
parameters. If A1-01
Setting Range
Default
0 or 1
Determined by A1-06
<1>
Application
5
135