◆ b8: Energy Saving

The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient
level.
Note: 1. Energy Saving is mainly designed for applications with variable torque (Normal Duty) but is not appropriate for applications where
the load may suddenly increase.
2. As the performance of the Energy Saving function strongly depends on the accuracy of the motor data, always perform Auto-Tuning
and make sure the motor data has been entered correctly before using this function.
b8-01: Energy Saving Control Selection
Enables or disables the Energy Saving function.
No.
b8-01
Setting 0: Disabled
Setting 1: Enabled
b8-02: Energy Saving Gain (OLV, CLV)
Sets the gain level for Energy Saving. A higher value results in lower magnetization of the motor and thereby less energy
consumption. However, if b8-02 is too low, the motor may stall.
No.
b8-02
b8-03: Energy Saving Control Filter Time Constant (OLV, CLV)
Parameter b8-03 sets the response time for Energy Saving. Although lowering this value allows for a quicker response,
instability may result if it is too low.
No.
b8-03
b8-04: Energy Saving Coefficient Value (V/f, V/f w/PG)
Parameter b8-04 is used to fine-tune Energy Saving control. The default setting depends on the capacity of the drive.
Adjust this setting while viewing the output power monitor (U1-08) and running the drive with a light load.
A low setting results in less output voltage and less energy consumption, but too small a value will cause the motor to
stall.
No.
b8-04
Note: This default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically
when Auto-Tuning for Energy Saving is performed
b8-05: Power Detection Filter Time (V/f, V/f w/PG)
The Energy Saving function continuously searches out the lowest output voltage in order to achieve minimum output
power. Parameter b8-05 determines how often the output power is measured in ms.
Reducing this setting will increase the response time. If the filter time is too short, the motor may become unstable with a
lighter load.
No.
b8-05
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Energy Saving Control Selection
Name
Energy Saving Gain
Name
Energy Saving Control Filter Time Constant
Name
Energy Saving Coefficient Value
(Refer to Auto-Tuning on page
Name
Power Detection Filter Time
5.2 b: Application
Setting Range
0 or 1
Setting Range
0.0 to 10.0
Setting Range
0.00 to 10.00 s
Setting Range
0.00 to 655.00
C6-01, E2-11, and o2-04
109).
Setting Range
0 to 2000 ms
Default
Determined by A1-02
Default
Determined by A1-02
Default
Determined by
A1-02 and o2-04
Default
Determined by
5
Default
20 ms
163