Control Circuit Wiring; Control Circuit Connection Diagram; Control Circuit Terminal Block Functions - YASKAWA A1000 Series Technical Manual

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

3.9 Control Circuit Wiring

3.9
Control Circuit Wiring

◆ Control Circuit Connection Diagram

Refer to Standard Connection Diagram on page 54

◆ Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S8), multi-function digital
outputs (M1 to M6), multi-function analog inputs (A1 to A3), and multi-function analog monitor output (FM, AM). The
default setting is listed next to each terminal in
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive
with untested control circuits could result in death or serious injury.
WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter A1-06 may change the I/O
terminal function automatically from the factory setting.
death or serious injury.
Input Terminals
Table 3.5
lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
input.
Type
No.
S1
Multi-function input 1 (Closed: Forward run, Open: Stop)
Multi-function input 2 (Closed: Reverse run, Open: Stop)
S2
Multi-function input 3 (External fault, N.O.)
S3
Multi-function input 4 (Fault reset)
S4
S5
Multi-function input 5 (Multi-step speed reference 1)
Multi-Function
Multi-function input 6 (Multi-step speed reference 2)
S6
Digital Inputs
Multi-function input 7 (Jog reference)
S7
Multi-function input 8 (External baseblock)
S8
SC
Multi-function input common
Digital input power supply +24 Vdc
SP
Digital input power supply 0 V
SN
Safe Disable input 1
H1
Safe Disable
H2
Safe Disable input 2
Inputs
Safe Disable function common
HC
Multi-function pulse train input (Frequency reference)
RP
Power supply for analog inputs
+V
Power supply for analog inputs
-V
Multi-function analog input 1 (Frequency reference bias)
A1
Analog Inputs /
Pulse Train Input
A2
Multi-function analog input 2 (Frequency reference bias)
Multi-function analog input 3 (auxiliary frequency
A3
reference) / PTC Input
Frequency reference common
AC
Ground for shielded lines and option cards
E (G)
72
when wiring terminals on the drive's control circuit.
Figure 3.1
Refer to Application Selection on page
Table 3.5 Control Circuit Input Terminals
Terminal Name (Function)
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
on page 54.
Function (Signal Level) Default Setting
Photocoupler
24 Vdc, 8 mA
Set the S3 jumper to select between sinking, sourcing mode, and the power supply.
Refer to
Sinking/Sourcing Mode Switch for Digital Inputs on page
Multi-function input common
24 Vdc power supply for digital inputs, 150 mA max (if no digital input option DI-
A3 is used only)
Never short terminals SP and SN as doing so will damage the drive.
24 Vdc, 8 mA
One or both open: Output disabled
Both closed: Normal operation
Internal impedance: 3.3 kΩ
Off time of at least 1 ms
Disconnect the wire jumpers shorting terminals H1, H2, and HC to use the Safe
Disable inputs. Set the S5 jumper to select between sinking, sourcing mode, and the
power supply as explained in
Sinking/Sourcing Mode Selection for Safe Disable
Inputs on page
77.
Safe disable function common
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
Input impedance: 3 kΩ
10.5 Vdc (max allowable current 20 mA)
-10.5 Vdc (max allowable current 20 mA)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by DIP switch S1 and H3-09
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
Use DIP switch S4 on the terminal board to selection between analog or PTC input.
0 V
103. Failure to comply may result in
77.
Page
423
77
518
137
241
136
136
234
136
137
236
136
136

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents