Fault Reset Methods - YASKAWA A1000 Series Technical Manual

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

◆ Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the
different ways to restart the drive.
After the Fault Occurs
Fix the cause of the fault, restart the drive, and
reset the fault
Resetting via Fault Reset Digital Input S4
If the above methods do not reset the fault, turn off the drive main power supply. Reapply power after the digital
operator display is out.
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. The Run command must first be removed
before a fault situation can be cleared.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Procedure
Press
on the digital operator.
Close then open the fault signal digital input via terminal S4.
S4 is set for "Fault Reset" as default (H1-04 = 14).
6.9 Diagnosing and Resetting Faults
DIGITAL OPERATOR JVOP-180
YEG
- MODE -
DRV
oC
Overcurrent
FWD
RESET
F1
RESET
ESC
RESET
RUN
Drive
Fault Reset Switch
S4 Fault Reset Digital Input
SC Digital Input Common
ON
2
OFF
1
ALARM
F2
LO
RE
ENTER
STOP
6
335

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents