Connecting A Pc - ABB ACS180-04S-03A7-1 Hardware Manual

Table of Contents

Advertisement

1
Drive. No J2.
2
Drive. J2 exists.
If your drive has jumper J2, follow the instructions below.
When you need to connect a PC or an assistant control panel to the drive, set:
Jumper J2 on the front of the drive = Panel (default)
Parameter 58.01 protocol enable = 0 (None, default)
When you need to use Modbus RTU communication with the drive, set:
Jumper J2 on the front of the drive = Modbus mode
Parameter 58.01 protocol enable = 1 (Modbus RTU)

Connecting a PC

To connect a PC to the drive, there are two alternatives:
Use an ACS-AP-I/S/W assistant control panel as a converter. Use a USB type
A – type Mini-B cable. The maximum permitted length of the cable is 3 m (9.8 ft).
Electrical installation 79