Miniature Circuit Breakers (Ul) - ABB ACS180-04S-03A7-1 Hardware Manual

Table of Contents

Advertisement

116 Technical data
ACS180-04...
-033A-2
-048A-2
-055A-2
3-phase U n = 380 ... 415V
-01A8-4
-02A6-4
-03A3-4
-04A0-4
-05A6-4
-07A2-4
-09A4-4
-12A6-4
-17A0-4
-25A0-4
-033A-4
-038A-4
-045A-4
-050A-4
1) Maximum permitted rated conditional short-circuit current (IEC 61800-5-1) of the electrical power
network.

Miniature circuit breakers (UL)

ACS180-04 drives are suitable for use on a circuit capable of delivering not more
than 10 kA symmetrical amperes (RMS) at 240 or 480Y/277 V maximum, when
protected by appropriate circuit breakers in the tables below. Additional fuse
protection is not required by UL when using circuit breakers herein. Circuit breakers
are not required to be in the same enclosure as the drive.
Type ACS180-
Frame
04...
1-phase U n = 208 ... 240 V
02A4-1
R0
Miniature circuit breaker
Frame
R3
R4
R4
R0
R0
R0
R1
R1
R1
R1
R2
R2
R3
R3
R4
R4
R4
Breaker type(UL)
SU202M-C8
ABB type
S203P-Z63NA
Contact ABB
Contact ABB
S203P-B4
S203P-B6
S203P-B6
S203P-B8
S203P-B10
S203P-B16
S203P-B16
S203P-B25
S203P-B32
S203P-B50
S203P-B63
S803S-B80
S803-B100
S803-B100
Minimum enclosure volume
1)
dm 3
15
Network SC
1)
kA
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2) 3)
in 3
890