Measuring The Insulation Resistance; Measuring The Insulation Resistance Of The Drive; Measuring The Insulation Resistance Of The Input Power Cable; Measuring The Insulation Resistance Of The Motor And Motor Cable - ABB ACS180-04S-03A7-1 Hardware Manual

Table of Contents

Advertisement

62 Electrical installation

Measuring the insulation resistance

Measuring the insulation resistance of the drive

WARNING!
Do not do voltage withstand or insulation resistance tests on the drive. The
tests can cause damage to the drive. Every drive is tested for insulation
between the main circuit and the chassis at the factory. Also, there are
voltage-limiting circuits inside the drive which cut down the testing voltage
automatically.

Measuring the insulation resistance of the input power cable

Before you connect the input power cable to the drive, measure its insulation
resistance according to local regulations.

Measuring the insulation resistance of the motor and motor cable

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or
death, or damage to the equipment can occur. If you are not a qualified
electrical professional, do not do installation, commissioning or
maintenance work.
1.
Do the steps in section
the work.
2. Make sure that the motor cable is disconnected from the drive output terminals.
3. Measure the insulation resistance between each phase conductor and the
protective earth conductor. Use a measuring voltage of 1000 V DC. The
insulation resistance of an ABB motor must be more than 100 Mohm (reference
value at 25 °C [77 °F]). For the insulation resistance of other motors, refer to
the manufacturer's instructions.
Note: Moisture inside the motor reduces the insulation resistance. If you think
that there is moisture in the motor, dry the motor and do the measurement
again.
1000 V DC,
> 100 Mohm
Electrical safety precautions (page 16)
ohm
U1
U1-PE, V1-PE, W1-PE
M
V1
3~
W1
PE