54 Guidelines for planning the electrical installation
3
min. 200 mm (8 in)
2
1
Motor cable
2
Input power cable
3
Control cable
4
Brake resistor or chopper cable (if any)
General guidelines – North America
Make sure that the installation is in accordance with national and local codes. Obey
these general guidelines:
Use separate conduits for the input power, motor, brake resistor (optional),
and control cabling.
Use separate conduit for each motor cabling.
The following figure illustrates the cable routing guidelines with an example drive.
min. 300 mm (12 in)
2
min. 300 mm (12 in)
2
90°
1
min. 500 mm (20 in)
3
1
4
4
min. 500 mm (20 in)
3

Advertisement