Switching On The Device; Further Information - Endress+Hauser Liquiphant FTL64 Brief Operating Instructions

Point level switch for liquids in high-temperature applications
Hide thumbs Also See for Liquiphant FTL64:
Table of Contents

Advertisement

Liquiphant FTL64 HART
7.4
Access to the operating menu via the operating tool
For more information, see the Operating Instructions.
8
Commissioning
8.1
Preparations
WARNING
L
The settings of the current output are relevant for safety!
Incorrect settings may cause the product to overflow or a pump to run dry.
The setting for the current output depends on the setting in the Assign PV parameter.
After changing the setting of the current output: check the settings for the range (Lower
range value output (LRV) and Upper range value output (URV)) and reconfigure them if
necessary!
8.1.1
As-delivered state
If no customized settings were ordered:
• Assign PV parameter Level limit detection (8/16 mA mode)
• MAX safety mode
• Alarm condition set to min. 3.6 mA
• DIP switch for locking in OFF position
• Bluetooth switched on
• Density range > 0.7 g/cm³ (43.7 lb/ft³)
• Switching times 0.5 s when the fork is covered and 1.0 s when it is uncovered
• HART burst mode switched off
8.2

Switching on the device

All configuration tools provide a commissioning assistant that supports the user when
setting the most important configuration parameters (Guidance menu Commissioning
wizard).
8.3

Further information

Further information and the documentation currently available can be found on the
Endress+Hauser website:
Endress+Hauser
www.endress.com
→ Downloads.
Commissioning
27