Q90R R-GAGE® Radar Sensor Instruction Manual
NOTE: If a factory reset is performed through the Banner Radar Configuration Software, the remote input
wire becomes disabled (factory default setting). If the sensor is returned to factory defaults by using the
remote input wire, the input wire remains enabled and the rest of the settings are restored to factory
defaults.
5.4

Remote Teach

Use the following procedure to teach the first and second switch points.
1.
Pulse the remote input once. The green Power LED flashes, the amber LED is off, and the red LED is off.
2.
Present the first point.
3.
Teach the switch point.
Single-pulse the remote input.
4.
Present the second point.
5.
Teach the switch point.
Single-pulse the remote input.
5.5

Remote Setup

Use Remote Setup to set the output mode to set normally open or normally closed, change the analog slope, or set the teach
mode.
While in remote set up, pulsing the remote wire once configures output 1. For analog models, the slope of the output
changes. For discrete output, output 1 and output 2 options are identical.
Changing the Output Mode using remote input affects both the output configuration (normally open versus normally closed)
and the Teach mode. The output configuration change takes effect immediately and can be used to change the output
between normally open and normally closed or the analog slope without changing the switch point distance. The change in
Teach mode does not immediately change the switch point location, but will affect the behavior of the next remote Teach.
5.5.1

Analog Teach Modes

The default is to teach two separate points. With a positive slope, the first taught point is 4 mA and the second taught point is
20 mA.
If the two taught points are within 100 mm or less, the sensor views them as the same point. It considers that point as the 20
mA spot and sets the 4 mA spot at 150 mm. If a taught point is within the dead zone, the sensor sets that point at 150 mm.
18
Action
T
Action
T
© Banner Engineering Corp. All rights reserved.
Result
Teach Accepted
The green Power LED is off, the yellow LED
of the output being taught flashes while the
yellow LED of the output not being taught is
off. The red LED indicates signal strength.
Teach Not Accepted
The green Power LED continues to flash, the
yellow LED is off, and the red LED is off.
Retry teaching the first point.
Result
The green Power LED turns on.
Teach Accepted
The sensor returns to run mode.
Teach Not Accepted
The green Power LED remains off, the
yellow LED of the output being taught
continues to flash while the yellow LED of
the output not being taught is off.
Retry teaching the second point.