2.3.3.2 Dimensions of the Inverters

Both the two model's dimensions are the same as follows:
2" (5.08cm)

2.3.3.3 Torque Values Application Note

Load Terminal Block
Grid Terminal Block
Gen Terminal Block
Neutral / Ground Bus bars
Cover Screws
Battery Connection
Warning: DO NOT use Impact Drivers to Tighten Any Fasteners on the Sol-Ark
Avertissement: NE PAS utiliser de tournevis à percussion pour serrer les fixations du Sol-Ark.
2" Minimum Horizontal Clearance | 6" Minimum Vertical Clearance
Temperature Derating
DC: 90C-100C Shutdown @ 100C
AC: 75C-82C Shutdown @ 82C
Model Sol-Ark 30K-3P-208V/ Sol-Ark 60K-3P-480V
62 IN Lbs
62 IN Lbs
62 IN Lbs
62 IN Lbs
15.5 IN Lbs
Hand-Pressed Actuation Lever
Hand-Pressed Actuation Lever
19
2" (5.08cm)
7 NM
7 NM
7 NM
7 NM
1.75 NM