Advertisement

5.6 H: Terminal Functions
Setting 1A: During Reverse
The During Reverse digital output will close whenever the drive is turning the motor in the reverse direction.
Status
Open
Motor is driven in the forward direction or stopped.
Closed
Motor is driven in reverse.
Setting 1E: Restart Enabled
The Restart Enabled output will be closed once the fault restart function becomes active and will remain closed until a
successful restart is accomplished or the number of Auto Restart attempts as specified by L5-01 is reached.
Fault Restart on page 107
Setting 3C: LOCAL/REMOTE Status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
REMOTE: The selected external reference (b1-01/02 or MEMOBUS/Modbus) is used as frequency reference and Run command
Open
source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Setting 100 to 13D: Reverse Switching for Functions 0 to 3D
These settings reverse the switching status of the specified function. Set as 1, where the last two digits specify the
setting number of the function to be reversed.
Examples:
• To reverse the output for "8: During Baseblock", set "108".
• To reverse the output for "3C: Run command" set "13C".
u

H3: Analog Input Terminal A1 Settings

These parameters adjust the signal level and characteristics of the analog frequency reference input A1.
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
H3-01
Setting 0: 0 to 10 Vdc with Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0.
Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency
reference can be set from 0 to 100% with an analog input of 5 to 10 V. The frequency reference will be zero when the
analog input is between 0 and 5 V.
98
Output frequency
FWD Run command
REV Run command
During Reverse
Figure 5.25 Reverse Direction Output Example Time Chart
for details on automatic fault restart.
Name
Terminal A1 Signal Level Selection
Description
ON
OFF
Description
Setting Range
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
time
Refer to L5:
Default
0 to 3
0