7 WIRING CONNECTION

HGM9510 controller's rear as following:
Description of terminal connection:
NO.
Functions
1
B-
2
B+
3
Emergency stop
4
Fuel relay
5
Crank
6
Aux. output 1
7
Aux. output 2
8
Aux. output 3
9
Charger (D+)
10
Aux. input 1
11
Aux. input 2
12
Aux. input 3
13
Aux. input 4
14
Aux. input 5
15
Aux. input 6
16
Magnetic Pickup
HGM9510 Genset Parallel Unit
Cable
Size
2
2.5mm
Connected with negative of starter battery.
Connected with positive of starter battery. If wire
2
2.5mm
length is over 30m, better to double wires in parallel.
Max. 20A fuse is recommended.
2
2.5mm
Connected with B+ via emergency stop button.
2
1.5mm
B+ is supplied by 3 points, rated 16A
2
1.5mm
B+ is supplied by 3 points, rated 16A
2
1.5mm
B+ is supplied by 2 points, rated 7A
2
1.5mm
B+ is supplied by 2 points, rated 7A
2
1.5mm
B+ is supplied by 2 points, rated 7A
Connected with charger's D+ (WL) terminals. Be
2
1.0mm
hanging in the air If there is no this terminal.
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
0.5mm
Connected with Speed sensor, shielding line is