Figure 3-20 Preparing a cable terminal outside the cabinet
Select an appropriate cabling route based on the actual situation. The figure is for reference
only.
Step 4 Connect the cable with a crimped terminal to the corresponding copper bar.
Step 5 Clean up foreign matter inside the cabinet.
----End

3.2.5 Routing Cables (60 kVA, 100 kVA)

3.2.5.1 Top Cable Routing

Context
● The cable connection procedures for the UPS5000-E-60K-F60 and UPS5000-
● Route cables for the UPS from inside out.
Procedure
Step 1 Ensure the maintenance bypass switch is OFF. Open the front door and remove
the cover from the power distribution subrack, as shown in
3-22
Issue 05 (2024-01-30)
NO TE
NO TICE
E-100K-F100 are the same. The following describes how to connect cables for
the UPS5000-E-100K-F100.
shows the positions of copper bars.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
Figure
3-21.
Figure
70